General Data |
Product Brand |
Class 14 |
|
Design |
Full-voltage non-reversing motor starter |
|
Special Features |
ESP200 overload relay; Dual voltage coil |
|
Weight |
8 lb (3.63 kg) |
|
Dimensions (H × W × D) |
9.78 × 6.75 × 5.19 in (248 × 171 × 132 mm) |
|
Touch Protection |
Not finger-safe |
|
Max. Installation Altitude |
6,560 ft (2,000 m) |
|
Operating Temperature |
-4°F to 104°F (-20°C to 40°C) |
|
Storage Temperature |
-22°F to 149°F (-30°C to 65°C) |
|
Country of Origin |
Mexico |
Horsepower Ratings |
200/208 V AC |
25 hp |
|
220/230 V AC |
30 hp |
|
460/480 V AC |
50 hp |
|
575/600 V AC |
50 hp |
Contactor |
Size |
NEMA controller size 3 |
|
Main NO Contacts |
3 |
|
Max. Operating Voltage (AC 60 Hz) |
600 V |
|
Rated Operational Current (600 V AC) |
90 A |
|
Mechanical Life (Main Contacts) |
5,000,000 cycles (typical) |
Auxiliary Contacts |
NO Contacts (at Contactor) |
1 |
|
NC Contacts (at Contactor) |
0 |
|
Max. Total Auxiliary Contacts |
7 |
|
UL Contact Rating |
10A@600VAC (A600), 2.5A@300VDC (Q300) |
Coil |
Control Supply Voltage |
AC 110–240 V (60 Hz) |
|
Holding Power (Min.) |
14 W |
|
Pick-up Power |
310 VA |
|
Holding Power |
26 VA |
|
Operating Voltage Range |
0.85–1.1 × rated value |
|
Drop-out Voltage |
50% of input voltage |
|
ON-Delay Time |
26–41 ms |
|
OFF-Delay Time |
14–19 ms |
Overload Relay |
Overload Protection |
Yes |
|
Phase Failure Detection |
Yes |
|
Asymmetry Detection |
Yes |
|
Ground Fault Detection |
Yes |
|
Test Function |
Yes |
|
External Reset |
No |
|
Reset Function |
Manual, automatic, remote |
|
Trip Class |
CLASS 5/10/20 (factory set)/30 |
|
Adjustable Current Range |
25–100 A |
|
Max. Tripping Time (Phase Loss) |
3 s |
|
Repeat Accuracy |
±1% |
|
Auxiliary Contacts (NO/NC) |
1 NO / 1 NC |
|
Aux. Contact Rating (UL) |
5A@600VAC (B600), 1A@250VDC (R300) |
|
Insulation Voltage (Single-Phase) |
600 V AC |
Mounting & Wiring |
Mounting Position |
Vertical |
|
Fastening Method |
Surface mounting |
Short-Circuit Rating |
Max. Breaking Capacity (I<sub>cu</sub>) |
14 kA@240V, 10 kA@480V/600V |
|
Required Fuse for Protection |
10kA@600V (Class H/K); 100kA@600V (Class R/J) |
|
Short-Circuit Trip Design |
Thermal magnetic circuit breaker |
Standards & Certifications |
Compliance |
NEMA ICS 2; UL 508; CSA C22.2 No.14 |
Ulasan